ABOUT U.S. REFERENCES CONTACT LOGIN
Language:

Products > PLC > Specifications


 
ParameterDescription
 
Scale ranges 4 inputs
actual temperature -20 .. 80 ° C in steps of 0.1 K (-50 .. 150 ° C)
 
control algorithmP, PI, PID / 2-point output signal with pulse width modulation (PWM 100 steps)
 
PWM cycle timeabout 100 seconds. (On the sum of the time. And off. PWM pulse width modulation)
 
indication4x20 character LCD display with simultaneous display of:
clock time, measured variables, inputs and outputs
 
state PWM4 x with the 0th resolution of .100% (4 0th .10 V)
 
alarm audible alarm every 30 seconds. (Siren for 5 sec.)
 
clock-Scale ranges 24 hours, 1-second increments
accuracy < 10 minutes / year (at 20 ° C)
ability to synchronize time from NTP server
 
operating temperature-20 .. 40°C
 
power supply12..24 VAC/VDC
 
cover body IP 20
 
category of protection device II
moisture categoryfreezing is not permitted
 






PLC TYP A



PLC TYP B



Displej